Gas and Specialty Sensors

KCD Series



Product Bar End
Product Bar End

KCD Series

Kele Carbon Dioxide Sensors KCD Series

Kele Carbon Dioxide Sensors

 

The Kele KCD Series carbon dioxide sensor was designed to offer an economical, reliable, non-dispersive infrared carbon dioxide sensor. The KCD carbon dioxide detector measures environmental CO2 levels for use in demand-controlled ventilation, air-quality monitoring, and other Building Automation Systems, BAS, HVAC applications in accordance with ASHRAE standards. Fully isolated voltage analog outputs and convenient flying leads on the wall mount make installation both simple and trouble-free. The analog output is available in 0-10 Volt DC or 4-20 mA, over the industry standard 0-2000 ppm CO2 range.


Products
Filter:

(Wholesale customers, log in for your special pricing)

QtyModelDescriptionIn StockList PriceInternet Price
KCD-D-A CO2 SENSOR DUCT MA OUTIn Stock363.00188.76
KCD-D-A-T24 CO2 SENSOR DUCT MA 10K OHM TYPE II THMS TEMPIn Stock373.00193.96
KCD-D-A-T3 CO2 SENSOR DUCT MA 10K OHM TYPE III THMS TEMPINFO373.00193.96
KCD-D-A-T85 CO2 SENSOR DUCT MA 1K OHM 385 RTD TEMPINFO373.00193.96
KCD-D-V CO2 SENSOR DUCT VDC OUTIn Stock339.00176.28
KCD-D-V-T24 CO2 SENSOR DUCT VDC 10K OHM TYPE II THMS TEMPIn Stock359.00186.68
KCD-D-V-T3 CO2 SENSOR DUCT VDC 10K OHM TYPE III THMS TEMPIn Stock359.00186.68
KCD-D-V-T85 CO2 SENSOR DUCT VDC 1K OHM 385 RTD TEMPINFO359.00186.68
KCD-W-A CO2 SENSOR WALL MA OUTIn Stock312.00162.24
KCD-W-A-T24 CO2 SENSOR WALL MA 10K OHM TYPE II THMS TEMPINFO323.00167.96
KCD-W-A-T3 CO2 SENSOR WALL MA 10K OHM TYPE III THMS TEMPINFO323.00167.96
KCD-W-A-T85 CO2 SENSOR WALL MA 1K OHM 385 RTD TEMPINFO323.00167.96
KCD-W-V CO2 SENSOR WALL VDC OUTIn Stock301.00156.52
KCD-W-V-T24 CO2 SENSOR WALL VDC 10K OHM TYPE II THMS TEMPINFO310.00161.20
KCD-W-V-T3 CO2 SENSOR WALL VDC 10K OHM TYPE III THMS TEMPIn Stock310.00161.20
KCD-W-V-T85 CO2 SENSOR WALL VDC 1K OHM 385 RTD TEMPINFO310.00161.20

Accessories

No accessories found
Features
  • 24 VAC/VDC power
  • 0-10 VDC or 4-20 mA output (0-5VDC on units with temperature option)
  • 0-2000 ppm CO2 range
  • Wall-mount and duct versions
  • Reverse polarity protected
  • Simple push-button calibration
  • Factory calibrated
  • Temperature option
Specifications

Supply Voltage:18-28 VAC @ 8 VA, 50/60 Hz, reverse polarity protection or 18-30 VDC @ 330 mA

Accuracy:±3% of reading or ±40 ppm

Signal Output:0-10V (10k min.) or 4-20 mA (600Ω max) (0-5V on Duct or wall w/ Temp only)

Repeatability:±20 ppm

Measurement Range:0-2000 ppm CO2

Sensing Technology:Non-dispersive IR (NDIR)

Calibration:Push button @ 2000 ppm

Calibration Interval:5 years

Life Expectancy:10 years typical

Visual Indication:Green 1000 ppm, Red > 2000 ppm

Warm Up Time:3 minutes

Response Time:<1 minute

Temperature:

Thermistor:10,000Ω Type II & III

RTD:1,000Ω Platinum 385 curve

Operating Temperature:31° to 122℉ (0° to 50℃)

Operating Humidity:0% to 99% RH (noncondensing)

Dimensions:

Wall:4.5"H x 2.8"W x 1.0"D (11.4 x 7.3 x 2.54 cm)

Duct:4.5"H x 2.8"W x 6.9"D (11.4 x 7.3 x 17.5 cm)

Duct probe:1.7″ (4.3 cm) diameter

 :6.25″ (15.9 cm) long

Weight:

Wall:0.25 lb (0.11 Kg)

Duct:0.5 lb (0.23 Kg)

Warranty:1 year

Certifications