Supply Voltage:
KCOP:20-30 VAC @ 5 VA or 24 VDC @ 200 mA, 50/60 Hz
LT Option:20-30 VAC @ 26 VA or 24 VDC @ 1.1 A, 50/60 Hz
Accuracy:
KCOP:±2.5% full scale
LT Option: ±4% full scale
Signal Output:
KCOP-R:Two SPDT relay contacts, 240 VAC, 2A resistive
KCOP-A: 4-20 mA @ 600Ω
Measurement Range:0-200 ppm
Sensing Technology:Electrochemical
Calibration:Recalibrate with 25 ppm CO gas
Visual Indication:Status Green: Power on, microprocessor operating properly; Yellow: Warning; Red: Alarm
Warm Up Time:Under 15 minutes
Response Time:
KCOP (all):30 Seconds to warning
KCOP-R:13 minutes to alarm
Sensing Technology:Electrochemical
Sensor Life Expectancy:Approximately 5 years
Relay Setpoints:Warning/alarm: 10/20 ppm, 25/50 ppm or 50/100 ppm, jumper selectable, (KCOP-R only)(5-10 ppm DIF)
Operating Temperature:32° to 122°F (0° to 50°C)
:(LT option) -22° to 122°F (-30° to 50°C)
Operating Humidity:5% to 99% noncondensing
Dimensions:6.50"H x 6.0"L x 2.13"D (16.5 x 15.2 x 5.4 cm)
Weight:
KCOP-A:3.5 lb (1.6 kg)
KCOP-R:4.0 lb (1.8 kg)
Warranty:1 year