UAT-1-47 | Kele | Transducers

UNIVERSAL ANALOG TRANSDUCER, ENCLOSURE, DIN RAIL

Brand:Kele

MPN:UAT-1-47

SKU:UAT-1-47

List Price:

$204.00

Today's Price:

$106.08

17 available to build
Tech Tip
The UAT's are half-wave rectified. Do not share a power tranformer with these and a full-wave device.
The UAT's are half-wave rectified. Do not share a power tranformer with these and a full-wave device.
Was this helpful?

product specifications

Mount

DIN rail

Type

Electronic

Output Signal

Analog, Digital

Input Signal

Analog

Supply Voltage (Nominal)

24 VAC, 24 VDC

product series specifications

Supply Voltage: 24 VAC ±10%, half-wave; or 24 VDC ±10%

Supply Current: 50 mA maximum @ 24 VDC; 100 mA maximum @ 24 VAC

Input: Jumper selectable and adjustable; Voltage ranges from 0-1.09 VDC (w/minimum span 55 mV) to 0-20 VDC (w/minimum span 1V); Current ranges from 0-4 mA (minimum span 0.2 mA) to 0-40 mA (minimum span 2.2 mA); Three-wire potentiometer ranges from 0-100O to 0-10 kO; Two-wire variable resistance ranges from 0-100O to 0-5 kO

Input Signal: DC voltage, current, or resistance

Input Impedance: 250kO @ 0-4 mA & 0-40 mA; 156kO @ 0-1.09 VDC & 0-10.9 VDC; 293kO @ 0-2 VDC & 0-20 VDC

Action: Direct or reverse acting

Linearity: <0.1% of span

Output: Jumper selectable and fully adjustable zero/span

Voltage: 0-18 VDC @ > 900O

Current: 0-10 VDC @ > 500O

Current: 0-20 mA @ < 650O

Output Current: For sensor excitation only, jumper selectable; 1.2 mA @ 5 kO maximum, 5 mA @ 1.5 kO maximum, 10 mA @ 750O maximum

Output Voltage: For sensor excitation only, jumper selectable; 1.2 VDC @ 12 mA maximum (100O minimum), 5 VDC @ 12 mA maximum (417O minimum), 10 VDC @ 12 mA maximum (834O minimum)

Wiring Terminations: Screw terminals

Operating Temperature: 32° to 158°F (0° to 70°C)

Operating Humidity: 5% to 95% RH (non-condensing)

Dimensions: UAT-1 3.0"H x 4.8"W x 1.5"D (8.6 x 5.1 x 12.4 cm) UAT-2 3.3"H x 4.6"W x 1.0" D (8.3 x 11.8 x 2.5 cm)

Weight: 0.8 lb (0.36 kg)

Warranty: 1 year

product series features

  • DC voltage, current, or resistive input
  • Inputs from 0-20 VDC, 0-40 mA or 0-10 VDC
  • Input and output jumper selectable and easily field calibrated
  • Outputs from 0-18 VDC or 0-20 mA
  • Direct or reverse acting, jumper selectable
  • Reference voltage and current available to power an input device or sensor

more information & related documents

Series Description

The UAT-1 and UAT-2 Series universal analog transducers are used for analog signal conversion or to scale signal. The analog signal converter will accept a DC voltage, current, or resistive input signal and output a non-isolated voltage or current output. These transducers can be direct or reverse acting and are easily field calibrated to meet a wide variety of applications in building automation systems, BAS. The UAT-1 is furnished in a unique slim-line design housing, which saves panel space, and can be ordered with an optional DIN rail mounting adapter. The UAT-2 is a snap-track mounted version and operates the same as the UAT-1.

Kele Description

UNIVERSAL ANALOG TRANSDUCER, ENCLOSURE, DIN RAIL

Manufacturer