L8148E1265 | Resideo | Thermostats & Controllers
AQUASTAT RELAY 180-240F
Brand:Resideo
MPN:L8148E1265
SKU:L8148E1265
product specifications
Type
AquaStat
Stages
Single
System Switching
No
Fan Switching
No
Controls Outputs
SPST
Supply Voltage (Nominal)
120 VAC
product series specifications
Sensing Element: 20' (6m) element, 1/8" dia., no bulb, controller operates at coldest point
Switch action
L480B: SPDT Automatic reset, makes R-B, breaks R-W on temperature fall
L480G: SPST Manual reset, breaks circuit on temperature fall
L482A: 2 SPST, manual reset, main switch (M2) opens, aux. switch (M1) closes on temperature fall
Switch Ratings: See Table 1 and Table 2 on Datasheet
Conduit Connection: 7/8" (22mm) hole for 1/2" conduit with 1-3/32" (28mm) knockout ring for 3/4" conduit
Setpoint Range
L480B, G: 20° to 60°F (-5° to 15°C)
L482A: 15° to 55°F (-9.4° to 13°C), with setpoint stops minimum 34°F
Setpoint Adjustment: Slotted screwdriver
Differential
L480B, G: Non-adjustable, additive, fixed at 10°F (6°C)
L482A: Non-adjustable, additive, fixed at 5°F (3°C)
Operating Temperature
L480B, G: -20° to 125°F (-11° to 52°C)
L482A: 20° to 140°F (-7° to 60°C)
Maximum Element Temperature
L480B, G: 225°F (107°C)
L482A: 250°F (121°C)
Dimensions
L480B, G: 3.3"H x 3.7"W x 2.3"D (8.4 x 9.4 x 5.9 cm)
L482A: 4.7" x 3.9"W x 2.1"D (11.9 x 10.1 x 5.3 cm)
Weight
L480B: 1.5 lb (0.68 kg)
L480G: 1.6 lb (0.73 kg)
L482A: 2.3 lb (1.04 kg)
Approvals: UL Listed file #E49725, Vol. No. 2, dated 02-09-66; Guide No. SDFY2 CSA Certified Listing G, File No. LR1620 ; Guide No. 400-E-0
Warranty: 1 year
product series features
- Dual temperature scale plate provides both Fahrenheit and Celsius readings
- No sensing bulb, the controller operates at the coldest point (1 foot section) of the 20 ft. element for complete coverage
- Dustproof and moisture proof enclosed switch for trouble-free operation
- Horizontal or vertical mounting for installation flexibility
more information & related documents
Series Description
The Honeywell L480 Series low limit controllers operate electric dampers, valves and compressor or fan motors to provide temperature or limit control of air conditioning systems and refrigeration units. The L480B has an SPDT switch and automatically resets; the L480G has an SPST switch that opens on a fall in temperature and requires manual reset. The L482A has two SPST switches and manual reset; the main switch opens, and the auxiliary switch closes, on a fall in temperature.
Kele Description
AQUASTAT RELAY 180-240F
Manufacturer
Resideo