BA/ZPMB-SR-NT-ND-BB | BAPI | Pressure Components

ZPM BAPI-BOX STANDARD RANGE, 1% ACCURACY, NO PROBE, NO DISPLAY

Brand:BAPI

MPN:BA/ZPMB-SR-NT-ND-BB

SKU:BA/ZPMB-SR-NT-ND-BB

List Price:

$225.00

Today's Price:

$117.00

Lead time of > 15 days. Chat with Kele experts now

product specifications

Accuracy

1%

Measurement

Inches of Water Column

Media Compatibility

Liquid, Gas

Range

0 - 5 in WC

Type

Multi

Display

No

product series specifications

Power:
13 to 40 VDC (4 to 20 mA Output)
7 to 40 VDC or 18 to 28 VAC (0 to 5V Output)
13 to 40 VDC or 18 to 28 VAC (0 to 10V Output)

Power Consumption:
20 mA max, DC only at 4 to 20 mA Output
7 mA max DC at 0 to 5 or 0 to 10 VDC Output
0.58 VA max AC at 0 to 5 or 0 to 10 VDC Output

System Accuracy: ±1.0% FS, 32 to 104°F (0 to 40°C)

Accuracy Low Range: ±0.02” WC (±4.98 Pa)

Accuracy Standard Range: ±0.1” WC (±24.9 Pa)

Accuracy High Range: ±0.3” WC (±74.65 Pa)

Temp Hysteresis & Stability: ±1% FS per year

Field Selectable Outputs: 4 to 20 mA, 0 to 5 V, 0 to 10 V

Load Resistance:
4 to 20 mA Output: 550? Maximum @ 24 VDC
Voltage Output: 6K? Minimum

Overpressure:
Low Range: Proof 300” WC (74 kPa)
Standard Range: Proof 300” WC (74 kPa)
High Range: Proof 500” WC (124 kPa)

Compensated Temp. Range: 2 to 122°F (0 to 50°C)

Environmental Operating Range: Temp: -4 to 140°F (-20 to 60°C)

Humidity: 0 to 95% RH, non-condensing

Storage Temp: -40 to 185°F (-40 to 85°C)

Media: Clean, dry, non-corrosive gases

product series features

  • 10 Pressure Ranges and 3 Output Options
  • Standard, Low and High Range Models Non-Flow-Through Sensor
  • NIST Certificate Available at No Extra Charge
  • Outputs, Ranges & Units Easily Set Without Power
  • Optional Display Aids in Troubleshooting by Showing the Actual Pressure Regardless of the Selected Range
  • Three Pressure Status LEDs for “Line of Sight Troubleshooting”
  • Simple Auto-Zeroing Process by Dead-Heading Low and High Ports and Pressing Auto-Zero Button

more information & related documents

Series Description

<p>BAPI’s Standard Accuracy ZPM in a BAPI-Box is designed forquick and easy field installation. Output, range and other variables arequickly set in the field without powering the unit. LEDs on the face of theunit indicate when the pressure is low, in range or high for line-of-sighttroubleshooting without accessing the BAS. Ranges and Outputs are set in thefield for this unit rather than at the time of order.</p>

Kele Description

ZPM BAPI-BOX STANDARD RANGE, 1% ACCURACY, NO PROBE, NO DISPLAY

Manufacturer

BAPI