605-2 | Dwyer Instruments | Pressure Components
Differential Pressure Indicating Transmitter, Range 0-2.0 W.C., Max. Pressure 2 psi (13.79 kPa), ±0.5% Electrical Accuracy, ±2% Mechanical Accuracy
Brand:Dwyer Instruments
MPN:605-2
SKU:605-2
List Price:
$1,023.00
Today's Price:
$531.96
Log in for customized pricingproduct specifications
Accuracy
2%
Connection
NPT
Dial Size
4.00 in
Direction
Uni-Directional
Filling
Dry
Measurement
Inches of Water Column
Media Compatibility
Liquid/Gas
Mount
Center Back
Output
4 - 20 mA
Range
±5 in WC
Type
Analog
Connection Size
1/8 in
Supply Voltage (Nominal)
24 VDC
product series specifications
- Supply Voltage 10-35 VDC, Two wire loop:
- Signal Output 4-20mA loop:
- Max Current Output Impedance 700Ω @24VDC, 10VDC min:
- Accuracy Includes (linearity, Repeatability, Hysteresis & Electrical):
- 605-(2,3,6) ±2.5% F.S. :
- 605-11 ±5% F.S. :
- Sensor Type Diaphragm in vertical position:
- Adjustments (Z/S) Protected potentiometers:
- Normal Measurement Range 0-6" WC:
- Available 0 to 500" WC, (Call Kele):
- Display 4" half dial w/ graduations per order:
- Overpressure (Burst) :
- Max Operating Pressure (Proof):
- 605-(2,3,6) 2 PSI (13.79 kPa):
- 605-11 25 PSI (172 kPa):
- Operating Temperature 20 to 120‚Ñâ (-6.67 to 48.9‚ÑÉ):
- Operating Humidity Not Specified:
- Wetted Parts Silicone, aluminum, acrylic, polycarbonate and steel:
- Media Compatibility Inert dry air:
- Process Connection Two (High/Low) 1/8" FNPT ports:
- Wiring Screw terminal block:
- Mounting 3 screws w/Vertical orientation:
- Enclosure Rating NEMA 1, Aluminum housing w/Clear Acrylic face:
- Dimensions 4.75 diameter (4.5" hole) x 1.69"D (12.6 (11.43) x 4.29cm):
- Weight 1 lb, 12.6 oz (811 g):
- Approvals CE, RoHS:
- Warranty 1 Year:
product series features
- Monitor pressures in ducts, rooms, or total building pressures
- Filter monitoring
- Local indication of clean room pressures with process signal sent to control room
more information & related documents
Series Description
The Series 605 Magnehelic® indicating transmitter provides for both visual monitoring and electronic control of very low differential pressure. The Series 605 is ideal for control applications in building HVAC systems where local indication is desired during routine maintenance checks or necessary when trouble shooting the system. The easily read dial gage is complimented by the two-wire, 4-20 mA control signal utilizing the time-proven Dwyer® Magnehelic® gage mechanical design and Series 600 transmitter technology. The two-wire design with terminal strip on the rear simplifies connection in any 4-20 mA control loop powered by a 10-35 VDC supply.
Kele Description
DIAL GAUGE, +/-2.00%, 0-2.00" WC, 4.00" DIAL, 1/8" CON, DRY, CENTER BACK MOUNT
Manufacturer
Dwyer Instruments
Related Documents