E50B1A | Veris | Power Monitoring & Protection
Pulse Output, 0.5% Acc., 90-600V; Current Transformer Integrator and power supply work in conjunction with the Veris E683 OR U018 CTs; Standard DIN rail, surface mounted, or NEMA 4 enclosure; Front-panel, Bright backlit LCD display; Phase alarm output contacts Pulse output commonly accepted by automation systems and data loggers; ANSI 12.20 0.5% accuracy, IEC 62053-22 Class 0.5S; Real energy output/phase loss alarm output on E50Bx and E5xCx models; 90-600 VAC; User-enabled password protection
Brand:Veris
MPN:E50B1A
SKU:E50B1A
List Price:
$-.--
Today's Price:
$-.--
Log in for customized pricingproduct specifications
Communication Protocol
PULSE
CT Inputs
3
Monitored Voltage
600 VAC
Monitored Current
32,000 A
product series specifications
Control Power, AC: 50/50 Hz; 5VA max; 90V min; UL Max: 600V(L-L) 347V (L-N); CE Max: 300V (L-N)
Control Power, DC: 3W max; UL and CE: 125 to 300VDC (external DC current limiting required)
Input Voltage:
UL: 90V (L-N) to 600V (L-L)
CE: 90V (L-N) to 300V (L-N)
Input Scaling: 20A to 5000A
Input Range: UO18 series rope style CTs only
Pulse Input (E5xHxA and E50FxA only): Contact inputs to pulse accumulators (one set with E5xH2A and E50F2A; two sets with E5xH5A and E51F5A)
Outputs: All (except E5xHxA and E50FxA):
Real Energy Pulse: N.O. static; Alarm contacts: N.C. static
E50BxA: Reactive Energy Pulse 30VAC/DC
E5xCxA: RS-485 2-wire Modbus RTU (1200 baud to 38.4 kbaud)
E5xHxA: RS-485 2-wire BACnet MS/TP (9600 baud to 115.2 kbaud)
E50FxA: 2-wire LON FT
Accuracy:
E50xxA: 0.5%
E51xxA: 0.2%
Operating Temperature: -22 to 158°C (-30 to 70°F)
Storage Temperature: -40 to 185°C (-40 to 85°F)
Operating Humidity:< 95% RH non-condensing
Mounting: DIN Rail or 3-point screw mount
Approvals: ANSI C12.20, California CSI Solar, EN61010, UL508
Warranty: 5 years
product series features
- Integrator and power supply for the CT's are built into the meter
- ANSI C12.20 0.5% accuracy on E50xxA
- ANSI C12.20 0.2% accuracy on E51xxA
- Works exclusively with Veris U018 Series rope CT's
more information & related documents
Series Description
The E5xxxA Series DIN rail meter combines exceptional metering performance with a built-in integrator and power supply to deliver an easily installed solution for power monitoring applications. Multiple communication protocol options offer added flexibility for system integration. E5xxxA devices work exclusively with Veris U018 series rope CTs for fast connection. The rope style CTs allow convenient installation in tight spaces. The data logging capability (E5xC3A and E5xx5A) protects data in the event of a power failure. Different devices in the series offer serial communication, pulse output, and phase alarms to suit a wide variety of applications. The E51xxA models add a bi-directional monitoring feature designed expressly for renewable energy applications, allowing measurement of power imported from the utility grid as well as power exported from the renewable energy source.
Kele Description
PULSE OUTPUT, 0.5% ACC., 90-600V, CT INTEGRATOR
Manufacturer
Veris
Related Documents