ESRN | Functional Devices | Network & Wireless
UL924 Enclosed Lighting Relay, 20 Amp SPST, 120-277 Vac Coil Input
Brand:Functional Devices
MPN:ESRN
SKU:ESRN
product specifications
Contact Type
SPST
Enclosure Rating
NEMA 1
Approvals
UL Listed, UL924, C-UL
Frequency
50/60 Hz
Operating Temperature
-30 to 140 °F (-35 to 60 °C)
Supply Voltage (Nominal)
277 VAC
product series specifications
Normal Power Supply Voltage: 120-277 Vac
Normal Power Current Draw: 24mA max
Normal Power Operating Frequency: 50/60Hz
Emergency Power Supply Voltage: 120-277 Vac
Emergency Power Current Draw: 118mA max
Emergency Power Operating Frequency: 50/60Hz
Remote Test Input (Class 2, Dry Contact): ESRTB or other switching method
Feedback/Dimmer Contact Switching Capability (Dry Contact Output): 130mA @ 250V max
Relay Contact SPST (ESRN): 20A Magnetic Ballast @ 277V, 16A Electronic Ballast @ 277V, 10A Tungsten @ 120V
Relay Contact SPST (ESRB): 10A Magnetic Ballast @ 277V, 10A Electronic Ballast @ 277V, 10A Tungsten @ 120V
Enclosure: UL Accepted for use in Plenum, NEMA 1
Wire: 16" 600V Rated
Weight: 0.675 lbs. (ESRN), 0.430 lbs (ESRB)
Operating Temperature: -30º to 140ºF (-35‚º to 60ºC)
Humidity Range: 5 to 95% (noncondensing), Rated for dry and damp locations only
Approvals: UL Listed, UL924, C-UL
Warranty: 5 years
product series features
- Automatic load control override
- Normal control of emergency lighting
- Coil input range: 120 Vac through 277 Vac
- LED indicators for normal voltage, emergency voltage, and load status
- 10 Amp and 20 Amp SPST magnetic ballast and tungsten ratings
- LED rating - Up to 16 Amp electronic ballast rating
- 0-10 Vdc dimmer override
- Remote control/test capability (model ESRTB)
- Nipple mount, wall mount, or ballast channel mount
- Made in the U.S.A.
more information & related documents
Series Description
When using the Functional Devices ESRN and ESRB UL924 relays, you have the capability for 0-10v dimming override, to enable full brightness when normal power is absent and emergency power becomes present. The ESRN or ESRB models will not only override the dimming, but will allow you to use the light fixture for both normal/emergency lighting when switching from a controller or wall switch application. These units have their own localized test button and LED indicators to assure the install was properly completed. Also, they include a 2.0 second delay test when the switch is deactivated, indicating the emergency circuit is active and ready. For scheduled remote testing, Functional Devices offers a remote dry contact test switch (ESRTB) to accompany the ESRN and ESRB models. This switch is used by field inspectors when testing the emergency circuit and their fixtures.