FS-EZ3-MOD-BAC | FieldServer | Network & Wireless
EZ Gateway, Modbus RTU - Modbus TCP - BACnet MS/TP - BACnet IP 500 point
Brand:FieldServer
MPN:FS-EZ3-MOD-BAC
SKU:FS-EZ3-MOD-BAC
product specifications
Power Supply
24 VAC/VDC
Type
RS-485 to Ethernet
Communication Input
Modbus
Communication Out
BACnet IP
product series specifications
- Supply Voltage:
- 12-24 VAC 50/60 Hz or 10-30 VDC
- Supply Current:
- 240 mA @ 12V
- Communication:
- Serial RS-485 x 2:
- Baud: 4800, 9600, 19200, 38400, 57600, 115200
- Ethernet:
- 10/100 BaseT MDIX
- Default IP:
- 192.168.2.101
- Subnet Mask:
- 255.255.255.0
- Connections:
- :
- Power 3 terminals
- :
- RJ485 6 terminals (2-ports)
- :
- Ethernet RJ45 (used for setup)
- Setup:
- :
- Web Based Internal HTML page
- :
- Diagnostics Web interface
- :
- BBMD Server Connect to remote BACnet networks
- :
- FS-EZ1 250 Registered points
- :
- FS-EZ2 500 Registered points
- Protocol:
- Modbus RTU, Modbus TCP/IP, BACnet MS/TP, BACnet/IP
- Gateway Operation:
- Modbus BACnet
- Operating Temperature:
- -40° to 167‚Ñâ (-40° to 75‚ÑÉ)
- Operating Humidity:
- 5-90% RH non-condensing
- Mounting:
- DIN rail, Wall MNT tabs or Tabletop
- Dimensions:
- 4.5‚Ä=H x 2.9‚Ä=W x 1.6‚Ä=D (11.5 x 7.4 x 4.1 cm)
- Weight:
- 0.4 lbs (0.2 Kg)
- Approvals:
- RoHS, CE, FCC, BTL Listed, CSA
- Warranty:
- 2 years
product series features
- Protocols supported: Modbus RTU, Modbus TCP/IP, BACnet MS/TP, BACnet/IP
- Any combination of Modbus to BACnet protocols can be selected
- Supports up to 500 or 1000 Modbus registers
- Supports BACnet Change of Value (COV) and BACnet Broadcast Distribution Device (BBMD)
- Easy to configure with the Web Interface via HTML page
- No additional software needed
- Diagnostics via the Web Interface
- Supports Modbus virtual nodes
- BTL approval marked
more information & related documents
Series Description
The FieldServer EZ Gateway offers System Integrators the tried and tested FieldServer protocols in an easy-to-use Modbus to BACnet Gateway. With the Profile Web Configuration Interface, profiles can be built in the field or in the office to be used time and time again on any EZ Gateway. Its two serial ports allow up to 64 Modbus RTU devices to be connected to one EZ Gateway. Modbus TCP/IP allows for fast responses from field devices using concurrent polling. It is ideal for integrators looking to minimize configuration time and commissioning costs, simplify training and start-up operations. Supports Modbus RTU, Modbus TCP/IP, BACnet MS/TP, BACnet/IP protocols.
Kele Description
MODBUS TO BACNET GATEWAY, 500 REGISTER POINTS
Manufacturer
FieldServer