DT-305 | Watt Stopper Legrand | Lighting Controls
CEILING MOUNT,24VDC PWR,NO LIGHT SENSOR OR
Brand:Watt Stopper Legrand
MPN:DT-305
SKU:DT-305
product specifications
Color
White
Mounting Location
Ceiling Mount
Sensing Type
Infrared
Supply Voltage (Nominal)
24 VDC
product series specifications
- Supply Voltage:
- :
- DT-300 24 VAC ±10% @ 1 VA, 24 VDC ±10% @ 43 mA
- :
- DT-305 24 VAC ±10% @ 0.8 VA, 24 VDC ±10% @ 35 mA
- Relay Output:
- :
- DT-300 Aux Volts out, Isolated Contact and light output
- :
- DT-305 Aux Volts out only on motion detect
- :
- Aux Output Motion initiated (Int.) 24VDC output
- :
- SPDT (300) Motion Int. contact, 30V (AC/DC) @1A
- :
- Light Output (300) Adjustable 10–300 fc to initiate a 24VDC output
- Technology:
- Passive Infra-Red (IR) w/ Fresnel lens
- :
- 40KHz Ultrasonic
- Occupied Mode (Occ):
- Occ.-Auto ON w/Single or both technologies w/TD OFF
- Approximate Coverage Pattern:
- :
- DT-300 360°, 12‚Äô ceiling/36‚Äô dia circle
- :
- DT-305 360°, 12‚Äô ceiling/40‚Äô dia circle
- Sensitivity:
- :
- Infrared 2 Dip switch settings Auto or Min
- :
- Ultrasonic POT Adjustment under cover
- :
- Light SP (300) Adjustable 10–300 fc to initiate a 24VDC output
- Override:
- Momentary DI input to simulate a "Motion Alert"
- OFF Delay Time (TD):
- DIP switches (5 seconds to 30 minutes)
- Indication:
- LED, Red (PIR) /Green (Ultra) w/enable-disable selection
- Mounting:
- Ceiling 3.5‚Ä= to 4‚Ä= hole
- :
- Octagonal box or ceiling direct w/spring clips
- Color:
- White
- Operating Temperature:
- 32°to 131‚Ñâ (0° to 55‚ÑÉ)
- Operating Humidity:
- 10-95% RH non-condensing
- Wiring:
- De-pluggable terminal strip, 4 (305) or 8 (300)
- Enclosure Rating:
- Indoor, No rating
- Dimensions:
- 4.5‚Ä= dia x 1.02‚Ä= deep (11.4 x 2.6 cm)
- Weight:
- 1.0 lb. (0.46 Kg)
- Approvals:
- UL File #E101196
- Warranty:
- 5 years
product series features
- SmartSet(™) automatically adjusts sensitivity and time delay
- Walk-through mode turns lights off
- Ultrasonic diffusion and PIR technology
- LED occupancy indication
- Pluggable terminal wiring
- Light level sensing with setpoint
more information & related documents
Series Description
The low-profile DT-300 dual-technology occupancy sensor with light level sensor combines the benefits of a passive infrared sensor (PIR) and ultrasonic technologies. The ceiling mount sensors feature a flat, unobtrusive appearance and provide 360 degrees of coverage. Using SmartSet™ technology, the DT-300 occupancy sensors require no adjustment at installation. SmartSet continuously monitors the controlled space to identify usage patterns. Using this information, the occupancy detector automatically adjusts the time delay and sensitivity settings for optimal performance and energy efficiency. Engineered specifically for building automation systems, BAS, and HVAC applications, the sensor assigns short delays (as low as 5 minutes) for times when the space is usually vacant, and longer delays (up to 30 minutes) for busier times. The DT-305 is a lower cost version of the DT-300 without isolated relay or light level sensor.
Kele Description
CEILING MOUNT,24VDC PWR,NO LIGHT SENSOR OR
Manufacturer
Watt Stopper Legrand
Related Documents