HF534-WD6XX14X | Rotronic Instrument | Humidity

Humditity Transmitter, 3 Wire 0-5 VDC, Wall Mount, Temperature & Enthalpy, No Keypad or Display, 1x ½ Conduit Adapter (Horizontal Mounting), 0° to 100°F (-18° to 38°C), Hydroclip Standard Climate Probe

Brand:Rotronic Instrument

MPN:HF534-WD6XX14X

SKU:HF534-WD6XX14X

List Price:

$1,205.00

Today's Price:

$626.60

Lead time of > 15 days. Chat with Kele experts now

product specifications

Accessory

691-K0A, DCPA-1.2, DCP-1.5-W, T81U-XR, T85U-XR, UR

Accuracy

0.8%

Application

Humidification, Dehumidification, Supply, Discharge, Return Air, Economizers, Clean Rooms, Data Centers, Process Control, Schools, Hospitals, Office Buildings

Housing Material

Poly

Mount

Room

Output

0 - 5 VDC

Probe Length

3.25 in

Temperature Range

32 to 212 °F (0 to 100 °C)

Power Requirements

24 VAC/VDC

product series specifications

Accuracy: ±0.8% RH @ 73°F (23°C) from 5% to 95% RH

Stability: 0.5% drift per year

Repeatability: 0.3% RH

Long Term Stability: <1% RH/year

Supply Voltage:

HF52: 10 to 28 VDC, 40 mA
HF53: 15 to 40 VDC, 50 mA; 12 to 28 VAC, 1.2 VA

Response Time:

RH: Typically 10 seconds for 63 % of a jump 35 to 80 %RH (1 m/sec air flow at sensor)

Temperature: Typically 4 seconds for 63 % of a change from 23 to 80 °C (1 m/sec air flow at sensor)

Signal Output: 4-20 mA @ 500 O

Range:

Humidity: 0-100%

Temperature: -148° to 392°F (-100° to 200°C)

Display: Optional: LCD, 1 or 2 decimals

Operating Humidity: 0 to 100% non-condensing

Operating Temperature: -40° to 140°F (-40° to 60°C)

Enclosure Rating: ABS/IP65 conforms to UL94-HB

Wiring Terminations: Screw terminals/ M16 cable gland or conduit adapter

Dimensions:

Case: 5.1"H x 5.1"W x 1.8"D (13 x 13 x 4.5 cm)

Wall Plate: 0.6"W x 3.5"L (1.5 x 9 cm)

Duct Probe: 0.6"W x 8.3"L (1.5 x 21 cm)

Approvals: CE/EMC: EMC Directive 2004/108/EC

Weight: 1 lb (0.45 Kg)

Warranty: 1 year

product series features

  • Interchangeable probe
  • Calculates all psychrometric values
  • Automatic sensor and drift compensation
  • Optional DIN rail mounting
  • Field configurable with software

more information & related documents

Series Description

The Rotronic HF5 Series high performance multi parameter humidity and temperature transmitters are ideal for all applications where exact measurement of humidity, enthalpy, dry bulb, wet bulb, temperatures plus other psychrometric parameters are critical. This high performance transmitter accurately measures relative humidity to within ±0.8% RH. The HydroClip2 probe can be individually calibrated and adjusted to increase measurement precision where you need it the most. The HF5 Series is available in a duct mount or wall mount configuration. This unit can be factory configured or software is available for field configuration.

Kele Description

WALL, TEMP AND ENT, NO DISPLAY, 0-100F, 0-100 ENT, 3 WIRE, 0-5 V

Manufacturer