PMRMCCLRB | Greystone Energy Systems | Gas & Specialty Sensors
PARTICULATE XMTR, +/-10 UG/M3, 0 - 1000 UG/M3, FLD SEL OUT, 1 RELAY, LCD, POLY ENCL, BACNET
Brand:Greystone Energy Systems
MPN:PMRMCCLRB
SKU:PMRMCCLRB
List Price:
$803.00
Today's Price:
$417.56
Log in for customized pricingproduct specifications
Application
IAQ, VOC, Healthcare, Environmental, Food, Construction, Automotive
Measurement Range
0 - 1,000 ug/m3
Display
Yes
Output Signal
Communicating
product series specifications
Sensor: Laser scatter method (field replaceable)
Particulate Size: PM2.5 or PM10 (selectable)
Mass Concentration Range: 0 - 1000 ug/m3
Resolution: 1 ug/m3
Accuracy: ±10 ug/m3 (0 - 100 ug/m3), ±10% (100 - 1000 ug/m3)
Response Time: 1 second
Sensor Lifetime: >8 years
Consumption: 75 mA max @ 24 Vdc, 100 mA max @ 24 Vac
Output Signals: 4-20 mA (sourcing) or 0-5 Vdc / 0-10 Vdc (selectable)
Output Drive Capability:
Current: 550O max
Voltage: 5,000O min
Output Scale: 0 to 1000 ug/m3 (menu selectable)
BACnet MODEL:
Consumption: 50 mA max @ 24 Vdc, 80 mA max @ 24 Vac
Interface: MS/TP, 2 wire RS-485
Baud Rate: 9600, 19200, 38400, 57600, 76800, or 115200 (menu selectable)
Address Range: 0 - 127 (menu selectable)
MODBUS MODEL
Consumption: 50 mA max @ 24 Vdc, 80 mA max @ 24 Vac
Interface: MS/TP, 2 wire RS-485, RTU
Baud Rate: 9600, 19200, 38400, 57600, 76800, or 115200 (menu selectable)
Address Range: 1-255 (menu selectable)
TRI-COLOR LED (OPTIONAL):
Good: Green (0 - 50 ug/m3)
Moderate: Yellow (51 - 150 ug/m3)
Poor: Red (151 and up)
PM ALARM RELAY (OPTIONAL)
Contact Ratings: Form C (NO + NC), 2A @ 140 Vac, 2A @ 30 Vac
Relay Setpoint + Hysteresis: Programmable via menu
Relay Time Display: Programmable via menu
GENERAL
LCD Size: 35mm x 15mm (1.4" W x 0.6" H)
LCD Backlight: Enable or disable via menu
Display Values:
Mass Concentration: 0 - 1000 ug/m3
Air Quality Index: 0 - 500 AQI Good/Moderate/Poor (menu selectable)
Power Supply: 24 Vac/dc ±20% (non-isolated half-wave rectified)
Protection Circuitry: Reverse
product series features
- Innovative contamination resistance technology to perform highly accurate and reliable PM measurements
- Uses an optical sensor based on laser scattering principles
- Measures particles of PM2.5 and PM10
more information & related documents
Series Description
The Greystone PMRMC particulate matter sensor uses an optical sensor based on laser- scattering principles and features innovative contamination resistance technology to perform highly accurate and reliable PM measurements. The replaceable sensor measures particles of PM2.5 and PM10 with a continuous-operation lifetime of more than eight years. The sensor will provide long-term reliability and high-resolution particle size binning for the detection of environmental dust and other particles.
Kele Description
PARTICULATE XMTR, +/-10 UG/M3, 0 - 1000 UG/M3, FLD SEL OUT, 1 RELAY, LCD, POLY ENCL, BACNET
Manufacturer
Greystone Energy Systems