PMDTBXX | Greystone Energy Systems | Gas & Specialty Sensors
DUCT PM TRANS, POLY ENCL W/ HINGED AND GASKETED COVER, NO RELAY, NONE
Brand:Greystone Energy Systems
MPN:PMDTBXX
SKU:PMDTBXX
List Price:
$976.00
Today's Price:
$507.52
Log in for customized pricingproduct specifications
Application
IAQ, VOC, Healthcare, Environmental, Food, Construction, Automotive
Measurement Range
0 - 1,000 ug/m3
Display
No
Output Signal
Voltage, Current
product series specifications
SENSOR | Laser scatter method (field replaceable) |
PARTICULATE SIZE | PM1.0, PM2.5, PM4.0, or PM10 (selectable) |
MASS CONCENTRATION RANGE | 0 - 1000 ug/m3 |
RESOLUTION | 1 ug/m3 |
ACCURACY | ±10 ug/m3 (0 - 100 ug/m3), ±10% (100 - 1000 ug/m3) |
RESPONSE TIME | 1 second |
SENSOR LIFETIME | >8 years |
TRI-COLOR LED | Good:Green (0 to 50 ug/m3) Moderate:Yellow (51 to 150 ug/m3) Poor:Red (151 to 1000 ug/m3) |
PM ALARM RELAY (OPTIONAL) | Contact Ratings:Form C (NO + NC), 2A @ 140 Vac, 2A @ 30 Vac Setpoint + Hysteresis:Programmable via menu Relay Time Delay:Programmable via menu |
LCD SIZE | 35mm W x 15mm H (1.4” x 0.6”) |
LCD BACKLIGHT | Enable or disable via menu |
DISPLAY VALUE | Mass Concentration:0 - 1000 ug/m3 Air Quality Index:0 - 500 AQI Good/Moderate/Poor (menu selectable) |
POWER SUPPLY | 24 Vac/dc ±20% (non-isolated half-wave rectified) |
PROTECTION CIRCUITRY | Reverse voltage protected; over-voltage protected |
OPERATING CONDITIONS | -10 to 60°C (14 to 140°F), 20 to 80 %RH non-condensing |
STORAGE CONDITIONS | -40 to 70°C (-40 to 158°F) |
ENCLOSURE |
Material:Polycarbonate, Grey, UL95-V0, IP65, (NEMA 4X) Dimensions:116mm W x 100mm H x 54mm D (4.6” x 3.9” x 2.1”) Probe:22.5mm D x 152mm L (0.88” x 6”) |
WIRING | Screw terminal block (14 to 22 AWG) |
COUNTRY OF ORIGIN | Canada |
product series features
- Laser scatter method sensor
- Highly accurate and reliable PM measurements
- Detection of environmental dusts and other particles
- LCD Display
- Network communication
more information & related documents
Series Description
<p>The PMDT Duct Particulate Matter Sensor uses an opticalsensor based on laser scattering principles and features innovativecontamination resistance technology to perform highly accurate and reliable PMmeasurements. The replaceable sensor measures particles of PM1.0, PM2.5, PM4.0,or PM10, with a continuous operation lifetime of more than 8 years. The sensorwill provide long-term reliability and high-resolution particle size binningfor the detection of environmental dust and other particles. A hinged andgasketed Polycarbonate enclosure is included for ease of installation.</p>
Kele Description
DUCT PM TRANS, POLY ENCL W/ HINGED AND GASKETED COVER, NO RELAY, NONE
Manufacturer