FASTUBE | Air Products | Gas & Specialty Sensors

THREE 24 IN SAMPLING TUBE SL-2000 FOR 6 FT

Brand:Air Products

MPN:FASTUBE

SKU:FASTUBE

List Price:

$45.45

Today's Price:

$23.63

Lead time of > 15 days. Chat with Kele experts now

product specifications

Type

ACCESSORY

product series specifications

Supply Voltage: Without accessories: 24 VAC @ 55 mA standby, 190 mA alarm

24 VDC @ 15 mA standby, 70 mA alarm

115 VAC @ 16 mA standby, 32 mA alarm

30 VAC @ 10 mA standby, 20 mA alarm

Frequency: 50/60 Hz

Relay Contacts: Alarm (2) SPDT, 10A, 115 VAC, resistive

Alarm (1) SPST-NO, 2A, 115 VAC, resistive

Trouble (1) SPDT, 10A, 115 VAC, resistive

Air Velocity: 100-4000 fpm (0.5-20.3 mps)

Radioactive Element: Americium 241, 0.9 µCi

Operating Temperature:

SL-2000-N: 32° to 158°F (0° to 70°C)

SL-2000-P: 32° to 140°F (0° to 60°C)

Operating Humidity: 10% to 85% RH non-condensing

Enclosure Rating: NEMA 1, Gray plastic back box, clear plastic cover

Dimensions: 4.5"H x 13.5"L x 2.25"D (11.4 x 34.3 x 5.7 cm)

Weight: 3.5 lb (1.6 Kg)

Warranty: 3 year

product series features

  • Low-flow technology, 100-4000 fpm
  • Universal voltage: 24 VAC, 24 VDC, 115 VAC, or 230 VAC
  • Two Form C and one Form A alarm contacts and one trouble contact
  • Interchangeable plug-in photoelectric or ionization heads
  • Compatible with building automation and fire alarm systems
  • Dust filtering included in detector head
  • Interconnect up to 30 detectors for common functions
  • Compatible with MS Series Remote Accessories
  • Cover removal trouble indication
  • Magnet test capability
  • Front or rear loading sampling tubes
  • Optional weatherproof enclosure

more information & related documents

Series Description

The Air Products & Controls SL-2000 Series Duct Smoke Detectors provide early smoke detection and sense combustion products present in air moving through HVAC ducts. Designed for use in building automation systems, BAS, each duct smoke detector uses intake sampling tubes to gather air samples. These are sold separately. A standard length exhaust tube is provided with each detector. These devices are designed to prevent the recirculation of smoke in areas by the air handling systems, fans and blowers. Complete systems may be shut down in the event of smoke detection.

Kele Description

THREE 24 IN SAMPLING TUBE SL-2000 FOR 6 FT

Manufacturer

Air Products