QIRF-R114X-0 | ACI | Gas & Specialty Sensors
Refrigerant Gas Sensor, R114, 0-1000 PPM, 4-20 mA, 2-10 VDC, 3 Relays, LCD, Plastic Enclosure, NEMA 4X
Brand:ACI
MPN:QIRF-R114X-0
SKU:QIRF-R114X-0
product specifications
Measurement Range
0 - 1,000 ppm
Mount
Wall
Type
Multi Refrigerant
Display
Digital
Output Type
Multiple
product series specifications
Supply Voltage: 18 to 30 VDC @ 1000 mA, 15 to 24 VAC @ 24 VA
Signal Output: 4-20 mA 600 O or 2-10 VDC (jumper selectable)
Accuracy: ±3% of reading
Measurement Range: 0-100 ppm R-123, 0-1000 ppm All others
Sensing Technology: Single pass, infrared non-dispersive
Gases Detected: (Model Specific) R-11, R-22, R-123, R-134a, R-404a, R-407c, R-408a, R-410a, R-114, R-116, R-438, R-507a
Alarm Relay Output: 3 alarm relays, 1 fault relay, SPDT, 30 VDC @ 1.0 A; 0.3 A @ 125 VAC
Communication Protocol: RS-485
Display: 2 x 8 character Backlight, and five LEDs
Buzzer: 80 dB
Operating Humidity: 5% to 95% RH non-condensing
Operating Temperature: -49 to 149°F (-45° to 65°C)
Dimensions: 4.7"H x 3.5"D x 7.9"L (12.0 x 9.0 x 20.0 cm)
Weight: 1.5 lb (0.68 Kg)
Warranty: 2 years
product series features
- Three alarm levels with SPDT alarm contacts
- 4-20 mA output signal
- Audible and visual alarm indication
- Infrared sensing technology
- Alarm-silence button
- NEMA 4 (IP66), 12, 13
- 1/2 in. barbed fitting (tubing not included)
more information & related documents
Series Description
The ACI Model QIRF Single Zone Refrigerant Gas Monitor is designed for continuous monitoring of R11, R22, R123, R134a, R404a or R507a refrigerants. Three adjustable alarm levels with relay output designate leak, spill, and evacuation concentrations. Gas alarms and system fault conditions are indicated by visual and audible alarms. The Model QIRF provides a system fault relay output and a 4 to 20 mA output for integration with remote monitoring equipment or building management systems. The QIRF Single Zone Refrigerant Gas Monitor is designed to be used as part of a control system that helps to prevent the formation of a hazardous environment when properly installed and maintained.
Kele Description
FREON, INFRARED, R114, 0-1KPPM
Manufacturer
ACI