TGW-ACN-A | Senva | Gas & Specialty Sensors
TGUL, WALL, ANALOG, CO, NO2
Brand:Senva
MPN:TGW-ACN-A
SKU:TGW-ACN-A
List Price:
$1,245.00
Today's Price:
$647.40
Log in for customized pricingproduct specifications
Application
Industrial, Oil & Gas, Labs, Agriculture, Transportation, Mining
Measurement Range
0 - 10 ppm
Mount
Wall
Display
Yes
Output Signal
Voltage, Current
Output Type
Multiple
product series specifications
Power Supply:15-30VDC/24VAC(1), 4W max, 160mA max.
Analog Outputs:2 programmable outputs: 0-10V (default), 0-5V, 1-5V and 4-20mA (menu selectable)
CO output scaling: 0-200ppm (default), 0-1000ppm (menu selectable)
NO2 output scaling: 0-10ppm (default), 0-30ppm (menu selectable)
Temperature output scaling: -20 to 85°C
BACnet /Modbus:
Protocol RS-485: BACnet MS/TP, Modbus RTU, Modbus ASCII
Baud Rates: 9600, 19200, 38400, 57600, 76800, 115200
Fan Relay:
Fan relay characteristics: N.C. 1A@24/30VDC (50/60Hz) (no mains connection)
CO fan relay setpoint: 25ppm (default), 0-1000 ppm (menu selectable)
NO2 fan relay setpoint: 1ppm (default), 0-30ppm (menu selectable)
Alarm Relay (Analog model only):
Alarm relay characteristics: N.C. 1A@24/30VDC (50/60Hz) (no mains connection)
CO alarm relay setpoint: 100ppm (default), 0-1000 ppm (menu selectable)
NO2 alarm relay setpoint: 3ppm (default), 0-30ppm (menu selectable)
Display:3-1/2 digit LCD: Indicates CO ppm, NO2 ppm (menu selectable)
LEDs:Green, Yellow, Red: Green = Normal, Yellow = Relay, Red = Alarm
Audible Alarm Exposure:85dB Piezo transducer: 30 minutes above alarm setpoint per UL2034 (menu selectable)
CO Sensor Performance:
Type: Electrochemical
Accuracy: ±5% of default range(2) ±5%of reading above menu selectable)
Resolution: 1ppm
Certications: UL2034 Listed Component
Life expectancy: >7 years
Coverage Area: 5000-7500 square feet
NO SensorPerformance:
Type: Electrochemical
Accuracy: ±5% of default range(3) ±5% of default range(3) ±5%of reading above 20ppm
Resolution: 0.1ppm
Life expectancy: >7 years
Coverage Area: 5000-7500 square feet
Methane Sensor Performance:
Type: Catalytic
Detection Range: 0-50% LEL (Lower Explosive Limit)
Accuracy: 5% of range
Resolution: 1%LEL
Life expectancy: >5 years
Coverage Area: 5000 square feet
Propane Sensor Performance:
Type: Catalytic
Detection Range: 0-50% LEL (Lower Explosive Limit)
Accuracy: 5% of range
Resolution: 1%LEL
Life expectancy: >5 years
Coverage Area: 5000-7500 square feet
Operating Environment:
Temperature, continuous: -20 to 50°C
Humidity: 15-95% continuous, 0-95% intermittent
Max Elevation: 2000m
Enclosure (Wall & Duct):
Material: ABS/Polycarbonate
Dimensions: 4.0"h x 4.4"w x 2.1"d
Conduit Opening: Tapped 1/2" NPT
Rating: IP20
Enclosure (Metal):
Material & Enclosure Rating: Powder-coated steel/acrylic, NEMA 3R
Dimensions: 5.0"h x 4.3"w x 2.25"d
Opening: Dual air vents on the bottom of the enclosure
Mounting: Pre-drilled for 2x4" electrical box
Rating: IP20
Approvals:Compliance UL61010-1 Listed UL, cUL
Warranty: 7 years
product series features
- Cost-effective dual gas sensing and control
- Flexibility of analog output model
- Versatility with BACnet/Modbus model. High reliability reduces callbacks
- Easy to install
more information & related documents
Series Description
Senva TG UL Series wall and duct sensors can be ordered as individual sensors or as any dual combination of CO / NO2 / CO2 / Methane / Propane / Hydrogen / Oxygen / H2S / Ammonia / Refrigerants sensor in a shared enclosure. The analog output model features two outputs that support daisy chain wiring - multiple sensors may be used in a parallel sequence (0-10V) for cost-effective coverage of large areas. The unit can also act as a stand-alone controller, utilizing the relay for exhaust fan operation, or the output for direct control of a VFD. The BACnet/Modbus model supports BACnet MS/TP & Modbus network communication in one unit. Standard features include network auto-configuration, a programmable fan relay, LED indicators, integrated display, and audible alarm.
Kele Description
TGUL, WALL, ANALOG, CO, NO2
Manufacturer
Senva
Related Documents