KTS-234-V-D-LCD | Kele | Gas & Specialty Sensors
Kele Tri-Sense IAQ Transmitter, CO2, RH, VOC Gases, 0-10 VDC, Duct Mount, LCD
Brand:Kele
MPN:KTS-234-V-D-LCD
SKU:KTS234VDLCD
List Price:
$781.00
Today's Price:
$406.12
Log in for customized pricingproduct specifications
Application
IAQ, VOC, Healthcare, Environmental, Food, Construction, Automotive
Measurement Range
0 - 1,000 ppm
Display
Yes
Output Signal
Current
product series specifications
Supply Voltage: 18-28 VAC, 50/60 Hz @ 5 VA, reverse polarity protected or 18-30 VDC @ 298 mA
Accuracy: ±2.5% full-scale
CO: ±2.5% full-scale
CO2: ±3% of reading or ±40 ppm
Humidity: 5% of reading (20% to 80% RH)
VOC: ±10% ethanol
Signal Output: Analog 4-20 mA @ 500?, 0-10V
VOC: Stepped output (4, 12, 20 mA)
: (0, 5, 10V)
Measurement Range: CO: 0-200 ppm, CO2: 0-2000 ppm
Humidity: 0% to 100%
VOC: 0-1000 ppm ethanol
Sensing Technology: CO: Electrochemical, CO2: Non-dispersive IR (NDIR)
Humidity: Capacitive
VOC: Sintered metal oxide
Visual Indication: LED Flashes above alarm setpoint, Display Optional, four-digit LCD
Warm Up Time: <15 minutes (maximum accuracy)
Relay Output: Optional, SPST, N.O. 2A @ 24 VAC/VDC
Relay Setpoint: CO: Factory set at 20 ppm of CO (20 ppm DIF), CO2: Factory set at 1000 ppm of CO2 (5 ppm DIF)
Operating Temperature: 32° to 122°F (0° to 50°C)
Operating Humidity: 0% to 99% RH (noncondensing)
Dimensions: Wall: 4.5"H x 2.8"W x 1.0"D (11.4 x 7.3 x 2.54 cm), Duct: 4.5"H x 2.8"W x 6.9"D (11.4 x 7.3 x 17.5 cm)
Duct probe: 1.7" (4.3 cm) diameter, 6.25" (15.9 cm) long
Weight: Wall: 0.25 lb (0.11 Kg), Duct: 0.5 lb (0.23 Kg)
Warranty: 1 year
product series features
- Three-in-one sensor combinations
- LED status indication
- Pre-calibrated to 20 ppm CO or 1000 ppm CO2 levels
- 0-10V or 4-20 mA output
- Optional relay output
- Isolated power and output
- Simple push-button calibration
- Optional LCD display
more information & related documents
Series Description
The Kele KTS Series Tri-Sense transmitters combine three different sensors in a compact enclosure, reducing installation time and space required. The unit is designed to work in tandem with building automation systems to provide proper ventilation in enclosed spaces such as schools, offices, conference rooms, malls, and theaters. The CO, CO2, and RH sensors have an independent analog output for 0-10V or 4-20 mA, but the output type is the same. The output signal for the VOC is in steps from (4, 12, 20 mA) or (0, 5, 10V). The unit is pre-calibrated for LED indication with a factory default setting for the appropriate gas. The sensors are equipped with push-button calibration and an easily accessible calibration port for field maintenance. Optional LCD display and relay output are available. The optional LCD display is selectable for any one of the three sensed variables.
Kele Description
CO2/RH/VOC XMTR 10V OUT DUCT LCD
Manufacturer
Kele
Related Documents