KCD-W-V | Kele | Gas & Specialty Sensors

Carbon Dioxide Sensor, Wall Mount, 0-10 VDC

Brand:Kele

MPN:KCD-W-V

SKU:KCD-W-V

List Price:

$301.00

Today's Price:

$156.52



152 in stock

product specifications

Application

Greenhouse, Laboratory, Food & Beverage, IAQ, Parking Garage, Agricultural

Measurement Range

0 - 2,000 ppm

Mount

Wall

Display

No

Output Signal

Current

Output Type

0-10 VDC

product series specifications

Supply Voltage: 18-28 VAC @ 8 VA, 50/60 Hz, reverse polarity protection or 18-30 VDC @ 330 mA

Accuracy: ±3% of reading or ±40 ppm

Signal Output: 0-10V (10k min.) or 4-20 mA (600? max) (0-5V on Duct or wall w/ Temp only)

Repeatability: ±20 ppm

Measurement Range: 0-2000 ppm CO2

Sensing Technology: Non-dispersive IR (NDIR)

Calibration: Push button @ 2000 ppm

Calibration Interval: 5 years

Life Expectancy: 10 years typical

Visual Indication: Green = 1000 ppm, Red > 2000 ppm

Warm Up Time: 3 minutes

Response Time: <1 minute

Temperature:

Thermistor: 10,000? Type II & III

RTD: 1,000? Platinum 385 curve

Operating Temperature: 31° to 122°F (0° to 50°C)

Operating Humidity: 0% to 99% RH (noncondensing)

Dimensions:

Wall: 4.5"H x 2.8"W x 1.0"D (11.4 x 7.3 x 2.54 cm)

Duct: 4.5"H x 2.8"W x 6.9"D (11.4 x 7.3 x 17.5 cm)

Duct probe:1.7? (4.3 cm) diameter, 6.25? (15.9 cm) long

Weight:Wall: 0.25 lb (0.11 Kg), Duct: 0.5 lb (0.23 Kg)

Warranty: 1 year

product series features

  • 24 VAC/VDC power
  • 0-10 VDC or 4-20 mA output (0-5VDC on units with temperature option)
  • 0-2000 ppm CO2 range
  • Wall-mount and duct versions
  • Reverse polarity protected
  • Simple push-button calibration
  • Factory calibrated
  • Temperature option

more information & related documents

Series Description

The Kele KCD Series carbon dioxide sensor was designed to offer an economical, reliable, non-dispersive infrared carbon dioxide sensor. The KCD carbon dioxide detector measures environmental CO2 levels for use in demand-controlled ventilation, air-quality monitoring, and other Building Automation Systems, BAS, HVAC applications in accordance with ASHRAE standards. Fully isolated voltage analog outputs and convenient flying leads on the wall mount make installation both simple and trouble-free. The analog output is available in 0-10 Volt DC or 4-20 mA, over the industry standard 0-2000 ppm CO2 range.

Kele Description

CO2 SENSOR WALL VDC OUT

Manufacturer

Kele

x