Accuracy
1%
Type
Insertion Flow Meter
Pipe Size
2 in
Max Pressure
400 psi
Max Temperature
221 °F
product series specifications
Accuracy: ±1% of full scale
Velocity Range: 0.5 to 30 fps (.15 to 9.0 mps)
Repeatability: ±0.3% of full scale
Linearity: ±0.2% of full scale
Rangeability: 60:1
Connections: 2" MNPT (mount in Thredolet or tee)
Wiring: 20' (6.1 m) Belden 9320 two-conductor shielded cable
Media Compatibility: Hot water, chilled water, water/glycol (verify application is compatible with flow sensor materials of construction, check material compatibility resources prior to ordering)
Media Temperature Range: Maximum 221°F (105°C)
Maximum Pressure: 400 psig (2758 kPa) @ 100°F (37.8°C) media temperature
Materials Of Construction:
220B Standard construction is Admiralty brass UNS C44300 sleeve, glass-reinforced nylon impeller, Pennlon UHMWPE bearings, tungsten carbide shaft, glass reinforced PPS housing, and ethylene propylene EPDM o-rings (other materials available special order).
220SS Standard construction is 300 series stainless steel sleeve, glass-reinforced nylon impeller, Pennlon UHMWPE bearings, tungsten carbide shaft, glass reinforced PPS housing, and ethylene propylene EPDM o-rings (other materials available special order).
Dimensions: 7.1"H x 3" diameter (18.1 x 7.6 cm)
Weight: 4.1 lb (1.9 Kg)
Approvals: CE
Warranty: 1 year
more information & related documents
Series Description
The 220B brass water flow sensor and 220SS stainless steel water flow sensor are used in general to measure water flow in metallic or PVC pipes from 2-1/2 in. to 40 in. (6.4 to 101 cm) size. Each sensor can mount in a 2 in. NPT pipe saddle or Thredolet®. Positioning nuts on the three threaded retaining rods allow the sensor to be accurately positioned to a standard insertion depth of 1-1/2 in. into the pipe. When this insertion depth is maintained, and there are at least 10 upstream and 5 downstream diameters of straight uninterrupted flow, an accuracy of ±1% of actual flow rate can be obtained between flow velocities of 0.5 to 30 ft/sec. Ideal for Building Automation Systems, BAS, and HVAC applications, the standard 200 Series flow sensors are rated for water temperatures to 221 „‰. For higher temperature requirements, see the SDI Series.