A-1027 | Badger Meter | Flow

BRASS TAPPING ADAPTER

Brand:Badger Meter

MPN:A-1027

SKU:A-1027

List Price:

$214.00

Today's Price:

$111.28

3 in stock

product specifications

Type

Accessory

product series specifications

Accuracy: ±1% of full scale

Velocity Range: 0.5 to 30 fps (.15 to 9.0 mps)

Repeatability: ±0.3% of full scale

Linearity: ±0.2% of full scale

Rangeability: 60:1

Connections: 2" MNPT

Wiring: 20' (6.1 m) two-conductor 20 AWG U.L. Type PTLC shielded cable

Media Compatibility: Hot water, chilled water, water/glycol (verify application is compatible with flow sensor materials of construction, check material compatibility resources prior to ordering)

Media Temperature Range: Maximum 221°F (105°C)

Maximum Pressure:

225B 200 psig (2069 kPa) @ 100°F (37.8°C) media temperature

226B, 226SS 400 psig (2758 kPa) @ 100°F (37.8°C) media temperature

Materials Of Construction:

225B, 226B Standard construction is Admiralty brass UNS C44300 sleeve, glass-reinforced nylon impeller, Pennlon UHMWPE bearings, tungsten carbide shaft, glass reinforced PPS housing, and ethylene propylene EPDM o-rings (other materials available special order).

226SS Standard construction is 300 series stainless steel sleeve, glass-reinforced nylon impeller, Pennlon UHMWPE bearings, tungsten carbide shaft, glass reinforced PPS housing, and ethylene propylene EPDM o-rings (other materials available special order).

Dimensions: 18"H x 3" diameter (46 x 7.6 cm) plus valve handle

Weight:

225B 17.5 lb (7.9 kg)

226B, 226SS 13.0 lb (5.9 kg)

HTT 12.0 lb (5.4 kg)

Approvals: CE

Warranty: 1 year

more information & related documents

Series Description

The 225B, 226B, 226SS Series hot tap flow sensors feature an elongated sensor, special mounting adapter, pipe nipple, and isolation valve. Indispensable in Building Automation Systems, BAS, and HVAC applications, each flow sensor features a nonmagnetic impeller sensor that can be installed into a pressurized pipe while the pipe is in service. The 225B, 226B, 226SS Series flow sensors can be used for pipe sizes 2-1/2 in. to 40 in. (6.4 to 101 cm). The hot tap flow sensor is recommended for any application where shutting down or draining a pipeline to remove the sensor for service is difficult.

Kele Description

BRASS TAPPING ADAPTER

Manufacturer

Badger Meter