59-546-12 | Fireye | Combustion Control & Flame Safety

8-conductor cable assembly with 8-pin female connector and Allen wrench. 12-meter (40') length. For Fireye Phoenix and Insight II flame detectors.

Brand:Fireye

MPN:59-546-12

SKU:59-546-12

List Price:

$969.23

Today's Price:

$504.00

Lead time of 5 days. Chat with Kele experts now

product specifications

Type

Cable Assembly

Used With

Fireye Phoenix and Insight II Flame Detectors

product series specifications

MECHANICAL:

Housing Material:

Standard Models and Model CEX-2: Cast aluminum with gray polyester powder coat finish

Model CEXSS: 316 stainless steel w/zinc primer, gray epoxy midcoat, polyurethane topcoat

Housing Weight:

Standard Models: 5.9 lbs. (2.69kg); CEX-2 Model: 13.2 lbs (5.98 kg)

Model CEXSS: 21.3 lbs. (9.66 kg); All other CEX Models: 7.1 lbs (3.22 kg)

Environmental: NEMA Type 4X / IP66, Class I Division 2, Groups A, B, C & D, Class II Division 2, Groups F& G (refer to agency approvals table)

Mounting: Requires one threaded mounting flange, ordered separately (see below). For fiber optic mount, refer to bulletin CU-117

Cooling / Purge Air Requirements:

Source: Clean, dry, cool

Volume: 4 SCFM (113 l/min) at 3/8” threaded mounting flange, or 1 inch “Y” fitting, mounted on scanner sight pipe. Temperature near the upper limit of the scanner operating range and/or use with dirty/dusty fuels may require up to 15 SCFM (425 l/min). Pressure: Adequate to overcome furnace or windbox pressure

Pressure: Adequate to overcome furnace or windbox pressure

Operating Temperature Rating: -40°F to + 150°F (-40°C to +65°C), ambient; -40°F to 176°F (-40°C to 80°C), scanner internal temperature

Storage Temperature Rating: -40°F to + 185°F (-40°C to +85°C)

Humidity: 0% to 95% relative humidity, non-condensing

ELECTRICAL:

Input Power: 24 Vdc, +10%, -15% supply current: 0.35 A, 8.5 VA, Hold Time must be 20 msec Min. Fireye power supply 60-2685 is recommended

Electrical Connection: 8-pin and 12-pin screw type quick-disconnect, (model 95DSS3-1)

Relay Output: 2 FLAME RELAYS, SPDT (N.O. and N.C.) ; FAULT RELAY, SPST (N.O.)

product series features

  • Combination infrared and ultraviolet sensors in one device
  • Two flame relays, fault relay, two 4-20 mA outputs standard
  • Works with intrinsically safe wireless handheld commissioning tool

more information & related documents

Series Description

Insight II integrated flame scanner uses both solid state infrared and ultraviolet sensors in a single device. The scanner's advanced sensors and algorithms accurately discriminate its target burner from adjacent flames in the same combustion chamber. The Type 95DSS3 scanner has two internal flame relays with adjustable On/Off thresholds, and two 4-20 mA analog outputs, eliminating the need for a remote flame amplifier. The Insight II scanner is the first Primary Safety Control to be UL-certified to Safety Integrity Level 3 (SIL3). If the target flame goes out, the scanner sends a signal to burner management system to close the fuel valve, preventing unburned fuel from entering the boiler, and eliminating the potential for explosion.

Kele Description

FIREYE 40FT/12M PRE-WIRED 59-546 CABLE ASSEMBLY FOR INSIGHT II/PHOENIX QUICK DISCONNECT SCANNER

Manufacturer

Fireye