MB-608E | Fireye | Combustion Control & Flame Safety

The MB-608E provides the capability to add up to eight flame sensing modules (MBPF-100S) to multi-burner control systems that require more than four burners. For systems monitoring 13 to 20 burners, two MB-608E expansion boards can be daisy chained together. Order with a 59-506-1 or 59-506-3 cable to connect the expansion board to the MB-600S.

Brand:Fireye

MPN:MB-608E

SKU:MB-608E

List Price:

$1,930.77

Today's Price:

$1,004.00

Lead time of 5 days. Chat with Kele experts now

product specifications

Type

Expansion Board

Used With

Fireye MB Industrial Multiburner Control System

product series specifications

Maximum Number of Burners: 20

Compatible Scanners: UV7A, UV7R4, UV7SC and Flame Rod

Valve Operation: Simultaneous (all burners operate from a single fuel train)

Supply Voltage: 120VAC (+10%, -15%), 50/60 Hz

Power Consumption: 25VA

Temperature Rating:

MB-600S: -40°C to +60°C (-32°F to +122°F)

MB-510 Display: 0°C to +50°C (-32°F to +122°F)

Flame Failure Response: 3 seconds (+/- 0.5 seconds)

Pilot Trial for Ignition: 5, 10, or 15 seconds (selectable)

Main Trial for Ignition: Follows Pilot Trial for Ignition selection

Purge Time: 0 seconds to 60 minutes (increment selectable depending on range)

Contact Ratings:

Fan Motor: 15 Amps Resistive (1/2 HP Inductive)

All Others: 10 Amps Resistive (1/3 HP Inductive)

Shipping Weight: 15 lbs (7 kilograms)

product series features

  • 3 second flame failure response time (±0.5 seconds)
  • 5-, 10-, or 15-second selectable pilot trial for ignition with 5-second pilot proving time
  • Compatible with UV7 ultravoilet flame scanners
  • Selectable purge time increments from 0-225 seconds in 15-second increments up to 0-60 minutes in 4-minute increments
  • UL recognized, FM approved

more information & related documents

Series Description

Fireye's MB multi-burner monitoring system controls the start-up sequence and monitors the flame of up to 20 individual gas, oil or combination gas/oil burners connected to a common valve train. Dynamic on-board diagnostics check for faulty relays, proof of valve closure, high and low fire switch interlocks, and shortened air switch. It can specifically identify which burner caused the initial flame failure. The MB-600S chassis directly powers pilot and main gas valves and ignition transformers. The built in blower output, purge timing and modulation control, let you add independent limits and a controller to create a complete combustion control system for furnace, oven or other multi-burner applications.

Kele Description

EXPANSION MODULE FOR UP TO 8 ADDITIONAL BURNERS

Manufacturer

Fireye